Page 442 - General Catalogue
P. 442
RWEYQ-T9
VRV IV water cooled+ series
Ideal for high rise buildings, using water as heat source
› Environmental conscious solution: reduced CO emmisions thanks › Variable Water Flow control option increases flexibility and control
2
to the use of geothermal energy as a renewable energy source › 2 analogue input signals allowing external control of ON-OFF,
and typical lower refrigerant levels making it ideal to comply with operation mode, error signal, …
EN378 › Contains all standard VRV features
› Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units,
Biddle air curtains and hot water
› Unique zero heat dissipation principle obviates the need
for ventilation or cooling in the technical room, maximising VRV-W
installation flexiblity Level difference between the VRV-W and indoor units:
› Wide range of indoor units: possibility to combine VRV with stylish 50m if the VRV-W is above
indoor units (Daikin Emura, Nexura, ...) 40m if the VRV-W is below
VRV-W
› Incorporates VRV IV standards & technologies: Variable Refrigerant Level difference between indoor units: 30m
Temperature, VRV configurator, 7-segment display and full inverter
compressors
› Developed for easy installation and servicing: choice between top Indoor installation Water piping
Unlimited water piping length
Refrigerant piping
or front connection for refrigerant piping and rotating switch box
for easy access to serviceable parts
› Compact & lightweight design can be stacked for maximum space
saving: 42HP can be installed in less than 0,5m2 floorspace
› 2-stage heat recovery: first stage between indoor units, second ErP 2021
COMPLIANT
stage between outdoor units thanks to the storage of energy in
the water circuit
› Unified model for heat pump and heat recovery version and Already fully compliant
to LOT 21 - Tier 2
geothermal and standard operation
Published data with
real-life indoor units
Connectable stylish indoor units
20 CLASS 25 CLASS 35 CLASS 42 CLASS 50 CLASS
Daikin Emura - Wall mounted unit FTXJ-MW/MS
Stylish - Wall mounted unit FTXA-A
Nexura - Floor standing unit FVXG-K
Floor standing unit FVXM-F
BPMKS box needed to connect RA indoors to VRV IV (RYYQ / RXYQ)
Access all technical information on RWEYQ-T9
at my.daikin.eu or click here
Outdoor unit RWEYQ 8T9 10T9 12T9 14T9
Capacity range HP 8 10 12 14
Cooling capacity Prated,c kW 22.4 28.0 33.5 40.0
Heating capacity Prated,h kW 25.0 31.5 37.5 45.0
Max. 6°CWB kW 25.0 31.5 37.5 45.0
Recommended combination 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB
ηs,c % 326.8 307.8 359.0 330.7
ηs,h % 524.3 465.9 436.0 397.1
SEER 8.4 7.9 9.2 8.5
SCOP 13.3 11.8 11.1 10.1
Maximum number of connectable indoor units 64 (1)
Indoor index Min. 100.0 125.0 150.0 175.0
connection Nom. -
Max. 300.0 375.0 450.0 525.0
Dimensions Unit HeightxWidthxDepth mm 980x767x560
Weight Unit kg 195 197
Sound power level Cooling Nom. dBA 65.0 71.0 72.0 74.0
Sound pressure level Cooling Nom. dBA 48.0 50.0 56.0 58.0
Operation range Inlet water Cooling Min.~Max. °CDB 10~45
temperature Heating Min.~Max. °CWB 10~45
Temperature around Max. °CDB 40
casing
Humidity around Cooling~Heating Max. % 80~80
casing
Refrigerant Type/GWP R-410A/2,087.5
Charge kg/TCO2Eq 7.9/16.5 9.6/20.0
Piping connections Liquid OD mm 952 127
Gas OD mm 19.1 (2) 22.2 (2) 28.6 (2)
HP/LP gas OD mm 15.9 (3) / 19.1 (4) 19.1 (3) / 22.2 (4) 19.1 (3) / 28.6 (4) 22.2 (3) / 28.6 (4)
Drain Size 14mm OD/ 10mm ID
Water Inlet/Outlet Size ISO 228-G1 1/4 B/ISO 228-G1 1/4 B
Total piping length System Actual m 500
Power supply Phase/Frequency/Voltage Hz/V 3N~/50/380-415
Current - 50Hz Maximum fuse amps (MFA) A 20 25
440