Page 438 - General Catalogue
P. 438
RQCEQ-P3
Replacement VRV, heat recovery
Quick & quality replacement for R-22 and R-407C systems
› Cost effective and fast replacement as only the outdoor and indoor
unit needs to be replaced, meaning almost no work has to be
carried out inside the building
› Efficiency gains of more than 40% can be realized, thanks to
technological developments in heat pump technology and the
more efficient R-410A refrigerant
› Less intrusive and time consuming installation compared to
installing a new system, as the refrigerant piping can be maintained
› Unique automatic refrigerant charge eliminates the need to
calculate refrigerant volume and allows safe replacement of
competitor replacement
› Automatic cleaning of refrigerant piping ensures a clean piping
network, even when a compressor breakdown has occurred
› Possibility to add indoor units and increase capacity without RQCEQ712-848P3
changing the refrigerant piping
› Possibility to spread the various stages of repclacement thanks to
the modular design of the VRV system
› Accurate temperature control, fresh air provision, air handling units
and Biddle air curtains all integrated in a single system requiring
only one single point of contact (RXYQQ-U only) ErP 2021
› Incorporates VRV IV standards & technologies: Variable Refrigerant COMPLIANT
› Temperature and full inverter compressors (RXYQQ-U only)
› Free combination of outdoor units to meet installation space or Already fully compliant
› efficiency requirements (RXYQQ-U only) to LOT 21 - Tier 2
Published data with
real-life indoor units
Access all technical information on RQCEQ-P3
at my.daikin.eu or click here
Outdoor unit System RQCEQ 280P3 360P3 460P3 500P3 540P3 636P3 712P3 744P3 816P3 848P3
System Outdoor unit module 1 RQEQ140P3 RQEQ180P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 RQEQ140P3 RQEQ180P3 RQEQ212P3
Outdoor unit module 2 RQEQ140P3 RQEQ180P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 RQEQ180P3 RQEQ212P3
Outdoor unit module 3 - RQEQ180P3 RQEQ212P3 RQEQ180P3 RQEQ212P3
Outdoor unit module 4 - RQEQ212P3
Capacity range HP 10 13 16 18 20 22 24 26 28 30
Cooling capacity Prated,c kW 28.0 36.0 46.0 50.0 54.0 60.0 70.0 72.0 78.0 80.0
Heating capacity Prated,h kW 32.0 40.0 52.0 56.0 60.0 67.2 78.4 80.8 87.2 89.6
Recommended combination 4 x FXMQ63P7VEB 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 4 x FXSQ32A2VEB 12 x FXSQ40A2VEB 3 x FXSQ40A2VEB 4 x FXSQ32A2VEB 4 x FXSQ32A2VEB 7 x FXSQ40A2VEB 4 x FXSQ40A2VEB
+ 2 x FXMQ63P7VEB + 2 x FXMQ80P7VEB + 8 x FXSQ40A2VEB + 9 x FXSQ50A2VEB + 9 x FXSQ40A2VEB + 6 x FXSQ40A2VEB + 9 x FXSQ50A2VEB + 12 x FXSQ50A2VEB
+ 3 x FXSQ50A2VEB + 6 x FXSQ50A2VEB
ηs,c % 200 185 191 201 198 186 194 204 187
ηs,h % 159 157 161 150 148 157 153 155 157
SEER -
SCOP -
Maximum number of connectable indoor units 21 28 34 39 43 47 52 56 60 64
Indoor index Min. 140 180 230 250 270 318 356 372 408 424
connection Nom. 280 360 500 540 636 712 744 816 848
Max. 364 468 598 650 702 827 926 967.0 1,061 1,102
Piping connections Liquid OD mm 9.52 12.7 15.9 19.1
Gas OD mm 22.2 25.4 28.6 34.9
Total piping System Actual m 300
length
Power supply Phase/Frequency/Voltage Hz/V 3~/50/400
Current - 50Hz Maximum fuse amps (MFA) A 30 40 50 60 70 80 90
Outdoor unit module RQEQ-P3 140P3 180P3 212P3
Dimensions Unit HeightxWidthxDepth mm 1,680x635x765
Weight Unit kg 175 179
Fan Air flow rate Cooling Nom. m³/min 95 110
Type Propeller fan
Sound power level Cooling Nom. dBA 79 83 87
Sound pressure level Cooling Nom. dBA -
Operation range Cooling Min.~Max. °CDB -5~43
Heating Min.~Max. °CWB -20~15.5
Refrigerant Type/GWP R-410A/2,087.5
Charge kg/TCO2Eq 10.3/21.5 10.6/22.1 11.2/23.4
Power supply Phase/Frequency/Voltage Hz/V 3~/50/380-415
Current - 50Hz Maximum fuse amps (MFA) A 15 20 22.5