Page 434 - General Catalogue
P. 434

RXYLQ-T

         VRV heat pump

         optimised for heating



         Where heating is priority without compromising         › Covers all thermal needs of a building via a single point of contact:
         on efficiency                                         accurate temperature control, ventilation, air handling units and
                                                               Biddle air cutains
            › Specifically developed for heating operation in low ambient     › Wide range of indoor units: possibility to combine VRV with stylish
           conditions, making it suitable for single source heating  indoor units (Daikin Emura, Nexura, ...)
            › Stable heating capacity down to -15°C, thanks to vapour injection     › Incorporates VRV IV standards & technologies: Variable Refrigerant
           compressor                                          Temperature, VRV configurator, 7 segment display and full inverter
            › Extended operation range down to -25°C in heating  compressors, 4-side heat exchanger, refrigerant cooled PCB, new
            › High reliability in severe conditions, thanks to hot gas bypass   DC fan motor, ...
           circuit in the heat exchanger                        › Free combination of outdoor units to
            › 15% increased heating capacity at high relative humidity   meet installation space or efficiency
           (2°CDB/1°CWB and RH=83%) vs previous model          requirements
            › Shorter defrost and heat up time, compared to standard VRV heat     › Wide piping flexibility: 30m indoor   ErP 2021
           pump                                                height difference, maximum piping     COMPLIANT
            › Very economical solution as a smaller outdoor unit model can be   length: 190m, total piping length: 500m
           used compared to the standard series                 › Less installation time and smaller   Already fully compliant
                                                                                                   to LOT 21 - Tier 2
                                                               footprint
               Access all technical information on RXYLQ-T     compared to previous model thanks to    Published data with
               at my.daikin.eu or click here                   removal of function unit        real-life indoor units
          Outdoor unit                       RXYLQ         10T                  12T                 14T
          Capacity range                        HP          10                  12                   14
          Cooling capacity  Prated,c            kW          28                  33.5                 40
          Heating capacity  Prated,h            kW         31.5                 37.5                 45
                      Max.  6°CWB               kW         31.50                37.50               45.00
          Recommended combination                      4 x FXMQ63P7VEB      6 x FXMQ50P7VEB  1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB
          ηs,c                                   %         251.4               274.4                270.1
          ηs,h                                   %         144.3                137.6               137.1
          SEER                                             6.36                 6.93                6.83
          SCOP                                             3.68                 3.51                 3.5
          Maximum number of connectable indoor units                           64 (1)
          Indoor index   Min.                               175                 210                 245
          connection  Nom.                                  250                 300                 350
                      Max.                                  325                 390                 455
          Dimensions  Unit  HeightxWidthxDepth  mm                          1,685x1,240x765
          Weight      Unit                      kg                              302
          Sound power level Cooling  Nom.      dBA          77                  81                   81
          Sound pressure level Cooling  Nom.   dBA          56                  59                   59
          Operation range  Cooling  Min.~Max.  °CDB                           -5.0~43.0
                      Heating  Min.~Max.       °CWB                           -25.0~16.0
          Refrigerant  Type/GWP                                              R-410A/2,087.5
                      Charge                  kg/TCO2Eq                        11.8/24.6
          Piping connections Liquid  OD        mm           9.5                           12.7
                      Gas   OD                 mm          22.2                           28.6
                      Total piping System  Actual  m                            500
                      length
          Power supply  Phase/Frequency/Voltage  Hz/V                       3N~/50/380-415
          Current - 50Hz  Maximum fuse amps (MFA)  A        25                             32
          Outdoor unit                       RXYLQ    16T     18T      20T      22T      24T     26T      28T
          System      Outdoor unit module 1         RXMLQ8T  RXYLQ10T  RXYLQ10T  RXYLQ10T  RXYLQ12T  RXYLQ12T  RXYLQ14T
                      Outdoor unit module 2         RXMLQ8T  RXMLQ8T  RXYLQ10T  RXYLQ12T  RXYLQ12T  RXYLQ14T  RXYLQ14T
          Capacity range                        HP    16       18       20      22       24       26       28
          Cooling capacity  Prated,c            kW   44.8     50.4      56      61.5     67      73.5      80
          Heating capacity  Prated,h            kW                               -
                      Max.  6°CWB               kW    50      56.5      63      69       75      82.5      90
          Recommended combination                  4 x FXMQ63P7VEB 3 x FXMQ50P7VEB 2 x FXMQ50P7VEB 6 x FXMQ50P7VEB 4 x FXMQ50P7VEB 7 x FXMQ50P7VEB 6 x FXMQ50P7VEB
                                                   + 2 x FXMQ80P7VEB + 5 x FXMQ63P7VEB + 6 x FXMQ63P7VEB + 4 x FXMQ63P7VEB + 4 x FXMQ63P7VEB + 5 x FXMQ63P7VEB + 4 x FXMQ63P7VEB
                                                                                      + 2 x FXMQ80P7VEB     + 2 x FXMQ80P7VEB
          ηs,c                                   %   261.8    255.7    251.4   263.0    274.4    270.8    270.1
          ηs,h                                   %   138.0    140.5    144.3    140.3   137.6    137.1    137.1
          SEER                                        3.52    3.59     3.68     3.58     3.51    3.50     3.50
          SCOP                                        6.62    6.47     6.36     6.65     6.93    6.84     6.83
          Maximum number of connectable indoor units                           64 (1)
          Indoor index   Min.                         280      315     350      385      420     455      490
          connection  Nom.                            400     450      500      550      600     650      700
                      Max.                            520     585      650      715      780     845      910
          Piping connections Liquid  OD        mm     12.7    15.9     15.9     15.9     15.9         19.1
                      Gas   OD                 mm     28.6    28.6     28.6     28.6             34.9
                      Total piping System  Actual  m                            500
                      length
          Power supply  Phase/Frequency/Voltage  Hz/V                       3N~/50/380-415
          Current - 50Hz  Maximum fuse amps (MFA)  A  40       45       50                   60


          432