INTRODUCTION
FXMQ-P7 / FXMQ-MB
Concealed ceiling unit
with high ESP
AIR PURIFIER
Ideal for large sized spaces
FXMQ-P7: ESP up to 200 Pa outblow
rear
› Possibility to change ESP via wired remote control allows suction
optimisation of the supply air volume bottom HEATING
› High external static pressure up to 200Pa facilitates extensive duct FXMQ50-80P7 suction
and grille network
› Discretely concealed in the wall: only the suction and discharge
grilles are visible
› Fresh air intake integrated in the same system thus reducing SPLIT
installation cost as no additional ventilation device is required
Fresh air intake opening in casing
Fresh air intake position
BRC1H519W7, BRC4C65
SKY AIR
› Standard built-in drain pump with 625mm lift increases flexibility
and installation speed
625 mm
* Brings in up to 10% of fresh air into the room VRV
› Flexible installation, as the air suction direction can be altered
from rear to bottom suction FXMQ-MB: ESP up to 270 Pa
› High external static pressure up to 270Pa facilitates extensive duct
and grille network
› Discretely concealed in the wall: only the suction and discharge VENTILATION & BID- DLE AIR CURTAINS
grilles are visible
› Large capacity unit: up to 31.5 kW heating capacity
External static pressure (Pa)
Automatic Airflow Adjustment function
Automatically selects the most appropriate fan curve to achieve the units’ nominal air flow within ±10% Fan characteristic Air flow (rated)
curves
Why? Air flow (actual) MARINE TYPES
After installation the real ducting will frequently differ from the initially calculated air flow resistance the real air flow may be much lower or higher than
nominal , leading to a lack of capacity or uncomfortable air temperature Duct resistance Air flow (with automatic
Automatic Airflow Adjustment function will adapt the unit’s fan speed to any ducting automatically (10 or more fan curves are available on every model), curves adjustment)
making installation much faster
± Air flow (m 3 /min)
Access all technical information on FXMQ-P7 Access all technical information on FXMQ-MB
at my.daikin.eu or click here at my.daikin.eu or click here CHILLERS
Indoor unit FXMQ 50P7 63P7 80P7 100P7 125P7 200MB 250MB
Cooling capacity Total capacity Nom. kW 5.6 7.1 9.0 11.2 14.0 22.4 28.0
Nom. kW -
Heating capacity Total capacity Nom. kW 6.3 8.0 10.0 12.5 16.0 25.0 31.5
Nom. kW -
Power input - 50Hz Cooling Nom. kW 0.110 0.120 0.171 0.176 0.241 0.895 1.185
Heating Nom. kW 0.098 0.108 0.159 0.164 0.229 0.895 1.185
Required ceiling void > mm 350 - FAN COIL UNITS
Dimensions Unit HeightxWidthxDepth mm 300x1,000x700 300x1,400x700 470x1,380x1,100
Weight Unit kg 35 46 132
Casing Material Galvanised steel plate
Decoration panel Model BYBS71DJW1 BYBS125DJW1 -
Colour White (10Y9/0.5) -
Dimensions HeightxWidthxDepth mm 55x1,100x500 55x1,500x500 -x-x-
Weight kg 4.5 6.5 -
Fan Air flow rate - Cooling Low/High m³/min 15.0/18.0 16.0/19.5 20.0/25.0 23.0/32.0 28.0/39.0 50/58 62/72 AIR HANDLING UNITS
50Hz Heating Low/High m³/min 15.0/18.0 16.0/19.5 20.0/25.0 23.0/32.0 28.0/39.0 -/-
External static Nom./High Pa 100/200 160/270 170/270
pressure - 50Hz
Air filter Type Resin net -
Sound power level Cooling Nom./High dBA -/61 -/64 -/67 -/65 -/70 75/76
Sound pressure level Cooling Low/High dBA 37/41 38/42 39/43 40/44 45/48
Heating Low/High dBA 37/41 38/42 39/43 40/44 -/-
Refrigerant Type/GWP R-410A/- R-410A/2,087.5 REFRIGERATION
Piping connections Liquid OD mm 6.35 9.52
Gas OD mm 12.7 15.9 19.1 22.2
Drain VP25 (I.D. 25/O.D. 32) PS1B
Power supply Phase/Frequency/Voltage Hz/V 1~/50/60/220-240/220 1~/50/220-240
Current - 50Hz Maximum fuse amps (MFA) A 16
Control systems Infrared remote control BRC4C65
Wired remote control BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 CONTROL SYSTEMS