Product specifications
Optimized energy efficiency both at full and part load conditions
Compact footprint through stacked heat exchanger lay-out
Heat pump version with reversibility on water side (up to 65°C hot water production)
Multiple options available: sound proof cabinet, rapid restart, removable electrical panel, etc. to adapt the unit to your specific application and need
One or two truly independent refrigerant circuits for outstanding reliability
Thanks to a large operating envelope, the unit is suitable for all possible process and comfort applications
High efficient flooded type heat exchanger allowing maximum unit performances
Benefits
Cooling only/Heating only EWWD-VZSS | 600 | 700 | 760 | 890 | C10 | C12 | C13 | C14 | C16 | C17 | C19 | C21 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity Nom. kW | 610 | 704 | 757 | 894 | 1.039 | 1.173 | 1.288 | 1.381 | 1.552 | 1.722 | 1.876 | 2.051 | |
Power input | Cooling Nom. kW | 110 | 132 | 142 | 162 | 196 | 231 | 252 | 276 | 315 | 339 | 380 | 404 |
Capacity control | Method | Variable | |||||||||||
EER | 5,5 | 5,31 | 5,3 | 5,52 | 5,29 | 5,07 | 5,11 | 5 | 4,93 | 5,08 | 4,93 | 5,08 | |
ESEER | 7,62 | 7,5 | 7,63 | 7,54 | 7,52 | 7,86 | 7,81 | 7,9 | 7,46 | 7,99 | 7,49 | 7,95 | |
Dimensions | Height mm | 2.123 | 2.292 | 2.487 | 2.296 | 2.350 | 2.338 | 2.498 | |||||
Width mm | 1.178 | 1.179 | 1.233 | 1.303 | 1.484 | 1.487 | 1.484 | 1.580 | 1.627 | 1.753 | |||
Depth mm | 3.722 | 3.750 | 3.690 | 3.822 | 4.792 | 4.508 | 4.750 | ||||||
Weight kg | 2.892 | 2.928 | 2.941 | 3.451 | 4.237 | 5.570 | 5.790 | 5.820 | 6.220 | 6.890 | 7.260 | 8.260 | |
Compressor | Type | Driven vapour compressor | |||||||||||
Quantity | 1 | 2 | |||||||||||
Refrigerant | Тype/GWP | R-134a/1.430 |