INTRODUCTION

                                                                                                       Selection




          Pair application selection
                                                                                                                     AIR   PURIFIER


            › the outdoor unit is connected to ONE COIL (with single circuit
           or maximum 3 interlaced circuits) using up to 3 control boxes
            › indoor unit combination is not allowed
                                                                                                                      HEATING
            › only works with X, W, Y control

          Step 1: Required AHU capacity                       Step 3: Control box selection

          An AHU with double flow, heat recovery and 100% fresh air is to   In this particular case, the control will work with precise air
          be installed in Europe where the outdoor sizing temperature is 35   temperature control. Only W or X control allow this. Since the   SPLIT
          ºCDB and the target supply air temperature for fresh air is 25 ºCDB.   consultant wants to use an “off-the-shelf” DDC module, the
          Load calculations point to a required capacity of 45kW.   EKEQFCBA box with W control allows easy set-up due to pre-set
          By checking on the EKEXV capacity table, for cooling operation,   factory values.
          40kW falls within the 400 class valve. Since 40kW is not the nominal
          capacity, a class adjustment has to be done. 40/45=0,89 and
          0,89x400=356. So the capacity class of the expansion valve kit is                                           SKY AIR
          356.
          Step  2: Outdoor unit selection

          For this AHU, a VRV IV heat pump model with continuous heating is
          going to be used (RYYQ-T series). For a capacity of 40kW at 35 ºCDB,                                        VRV
          an outdoor of 14HP (RYYQ14T) is selected. The capacity class of the
          14 HP outdoor unit is 350.

          Total connection ratio of the system is 356/350=102% hence it falls
                                                                                                                     VENTILATION & BID-  DLE AIR CURTAINS
          within the range 90-110%.





                                                                                                                      MARINE TYPES

          Multi application selection



            › the outdoor unit can be connected to MULTIPLE COILS
           (and their control boxes)
            › indoor units are also connectable but not mandatory                                                     CHILLERS
            › only works with Z control



          Step 1: Required AHU capacity                       Step  2: Outdoor unit selection
                                                                                                                      FAN COIL UNITS
          An AHU with double flow, heat recovery and 100% fresh air is to   For this system where a AHU is connected with indoor units,
          be installed in Europe where the outdoor sizing temperature is   it is mandatory to use a heat recovery unit. By consulting the
          35 ºCDB and the target supply air temperature for fresh air is 25   engineering databook for REYQ-T, the total required capacity of 42,5
          ºCDB. On top of this, for this building, 5 round-flow cassette units   kW requires a 16HP model REYQ16T. Which will deliver 45kW at the
          FXFQ50A will also be connected to this OU.          design temperature of 35 ºCDB. This unit has a capacity class of 400.
          Load calculations point to a required capacity of 20kW for the AHU   Total connection ratio of the system is 428/400=107% hence it falls   AIR HANDLING   UNITS
          and 22,5 kW for the indoor untis.                   within the range 50-110%.
          By checking on the EKEXV capacity table, for cooling operation,
          20kW falls within the 200 class valve. Since 22,4 kW is the nominal
          capacity, a class adjustment has to be done. 20/22,4=0,89 and
          0,89x200=178. So the capacity class of the expansion valve kit is   Step 3: Control box selection
          178. Total capacity class of the indoor unit system is 178+250=428                                          REFRIGERATION
                                                              In this particular case, the only available control is Z control and the
                                                              combination of AHU and VRV DX indoor units requires EKEQMCBA
                                                              control box.