Page 486 - General Catalogue
P. 486

VAM-FC9/VAM-J

                                                                                                  Diamond
          Energy recovery ventilation                               Return air                   shape heat

                                                                                                 exchanger!
                                                              Supply air
          Ventilation with heat recovery as standard


            › Thinnest High Efficiency Enthalpy Heat Exchanger
           in the market (J-series)
            › Energy saving ventilation using indoor heating,
           cooling and moisture recovery
            › Free cooling possible when outdoor temperature                                             Exhaust air
           is below indoor temperature (eg. during nighttime)                                 Fresh air
            › Prevent energy losses from over-ventilation while
           improving indoor air quality with optional CO  sensor
                                            2
            › Possibility to change ESP via wired remote control allows
           optimisation of the supply air volume (J - series)
            › Can be used as stand alone or integrated in the Sky Air
           or VRV system                                              High efficiency filters available:
            › Wide range of units: air flow rate from 150 up to 2,000 m³/h  ePM  70% (M6), ePM  55% (F7) and ePM  70% (F8)
                                                                    10       1          1
            › Shorter installation time thanks to easy adjustment
           of nominal air flow rate, so less need for dampers compared
           with traditional installation
            › No drain piping needed
            › Can operate in over- and under pressure                                                     ErP
                                                                                                         COMPLIANT
            › Total solution for fresh air with Daikin supply
           of both VAM / VKM and electrical heaters


          Ventilation                       VAM/VAM  150FC9  250FC9  350J  500J  650J  800J  1000J  1500J  2000J
          Power input - 50Hz Heat   Nom.  Ultra high/High/Low  kW 0.132/0.111/  0.161/0.079/  0.097 /0.070 / 0.164 /0.113 / 0.247 /0.173 / 0.303 /0.212 / 0.416 /0.307 / 0.548 /0.384 / 0.833 /0.614 /
                      exchange
                      mode                           0.058  0.064  0.039   0.054   0.081   0.103   0.137   0.191   0.273
                      Bypass mode Nom.  Ultra high/High/Low  kW 0.132/0.111/  0.161/0.079/ 0.085 /0.061 / 0.148 /0.100 / 0.195 /0.131 / 0.289 /0.194 / 0.417 /0.300 / 0.525 /0.350 / 0.835 /0.600 /
                                                     0.058  0.064  0.031   0.045   0.059   0.086   0.119   0.156   0.239
          Temperature   Ultra high/High/Low      %  77.0 (1) / 72.0 (2)/  74.9 (1) / 69.5 (2)/   85.1 /86.7 /  80.0 /82.5 /  84.3 /86.4 /  82.5 /84.2 /  79.6 /81.8 /  83.2 /84.8 /  79.6 /81.8 /
          exchange                                  78.3 (1) / 72.3 (2)/  76.0 (1) / 70.0 (2)/   90.1   87.6   90.5   87.7   86.1   88.1   86.1
          efficiency - 50Hz                         82.8 (1) / 73.2 (2)  80.1 (1) / 72.0 (2)
          Enthalpy exchange  Cooling  Ultra high/High/Low  % 60.3 (1)/61.9 (1)/  60.3 (1)/61.2 (1)/  65.2 /67.9/  59.2 /61.8 /  59.2 /63.8 /   67.7 /70.7 /  62.6 /66.4 /  68.9 /71.8 /  62.6 /66.4 /
          efficiency - 50Hz                          67.3 (1)  64.5 (1)  74.6   69.5   73.1   76.8   74.0   77.5   74.0
                      Heating  Ultra high/High/Low  % 66.6 (1)/67.9 (1)/  66.6 (1)/67.4 (1)/  75.5 /77.6 /  69.0 /72.2 /  73.1 /76.3 /   72.8 /75.3 /  68.6 /71.7 /   73.8 /76.1 /   68.6 /71.7 /
                                                     72.4 (1)  70.7 (1)  82.0   78.7   82.7   80.2   77.9   80.8   77.9
          Operation mode                                          Heat exchange mode, bypass mode, fresh-up mode
          Heat exchange system                                 Air to air cross flow total heat (sensible + latent heat) exchange
          Heat exchange element                                      Specially processed non-flammable paper
          Dimensions  Unit   HeightxWidthxDepth  mm   285x776x525   301x1,113x886  368x1,354x920  368x1,354x1,172  731x1,354x1,172
          Weight      Unit                       kg      24.0         46.5       61.5      79.0          157
          Casing      Material                                             Galvanised steel plate
          Fan         Air flow   Heat   Ultra high/High/   m³/h   350 (1)/   500 (1)/   650 (1)/   800 (1)/   1,000 (1)/   1,500 (1)/   2,000 (1)/
                             exchange
                      rate -   mode  Low           150 /140 /105  250 /230 /155   300 (1)/   425 (1)/   550 (1)/   680 (1)/   850 (1)/   1,275 (1)/   1,700 (1)/
                                                                                                     825 (1)
                                                                                       440 (1)
                                                                                              550 (1)
                                                                   200 (1)
                                                                                                           1,100 (1)
                                                                         275 (1)
                                                                                350 (1)
                      50Hz   Bypass mode Ultra high/High/   m³/h  350 (1)/   500 (1)/  650 (1)/  800 (1)/  1,000 (1)/  1,500 (1)/  2,000 (1)/
                                    Low            150 /140 /105  250 /230 /155   300 (1)/   425 (1)/  550 (1)/  680 (1)/  850 (1)/  1,275 (1)/  1,700 (1)/
                                                                   200 (1)  275 (1)  350 (1)  440 (1)  550 (1)  825 (1)  1,100 (1)
                      External static  Ultra high/High/Low  Pa 90 /87/40  70 /63/25   90 (1)/70.0 /50.0 (1)
                      pressure - 50Hz
          Air filter  Type                         Multidirectional fibrous fleeces  Multidirectional fibrous fleeces (G3)
          Sound pressure   Heat   Ultra high/High/Low  dBA  27.0 /26.0   28.0 /26.0   34.5 (1)/   37.5 (1)/   39.0 (1)/   39.0 (1)/   42.0 (1)/   42.0 (1)/   45.0 (1)/
                      exchange
          level - 50Hz  mode                         /20.5   /21.0   32.0 (1)/   35.0 (1)/   36.0 (1)/   36.0 (1)/   38.5 (1)/   39.0 (1)/   41.5 (1)/
                                                                                                           36.0 (1)
                                                                  29.0 (1)
                                                                                       30.5 (1)
                                                                                31.0 (1)
                                                                         30.5 (1)
                                                                                                    33.5 (1)
                                                                                             32.5 (1)
                      Bypass   Ultra high/High/Low  dBA  27.0 /26.5   28.0 /27.0   34.5 (1)/   38.0 (1)/   38.0 (1)/   40.0 (1)/   42.5 (1)/   42.0 (1)/   45.0 (1)/
                      mode                           /20.5   /21.0   32.0 (1)/   35.0 (1)/   34.5 (1)/   36.5 (1)/   40.0 (1)/   39.0 (1)/   41.0 (1)/
                                                                                       30.5 (1)
                                                                                30.5 (1)
                                                                                                           35.0 (1)
                                                                                                    32.5 (1)
                                                                                             32.5 (1)
                                                                         29.5 (1)
                                                                  28.0 (1)
          Operation range  Around unit          °CDB      -                     0°C~40°CDB, 80% RH or less
          Connection duct diameter              mm   100    150       200              250              2x250
          Power supply  Phase/Frequency/Voltage  Hz/V                      1~ ; 50/60 ; 220-240/220
          Current     Maximum fuse amps (MFA)     A      15.0                          16.0
          Specific energy   Cold climate      kWh/(m².a)  -56.0 (5)  -60.5 (5)          -
          consumption (SEC) Average climate   kWh/(m².a)  -22.1 (5)  -27.0 (5)          -
                      Warm climate            kWh/(m².a)  -0.100 (5)  -5.30 (5)         -
          SEC class                                D / See note 5 B / See note 5        -
          Maximum flow rate Flow rate           m³/h  130   207                         -
          at 100 Pa ESP  Electric power input    W    129   160                         -
          Sound power level (Lwa)                dB   40     43    51     54        58         61    62     65
          Annual electricity consumption       kWh/a  18.9 (5)  13.6 (5)                -
          Annual heating   Cold climate        kWh/a  41.0 (5)  40.6 (5)                -
          saved       Average climate          kWh/a  80.2 (5)  79.4 (5)                -
                      Warm climate             kWh/a  18.5 (5)  18.4 (5)                -

          (1)Measured according to JIS B 8628 | (2)Measured at reference flow rate according to EN13141-7 | (5) At reference flow rate in accordance with commission regulation (EU) No 1254/2014