Page 424 - General Catalogue
P. 424

RYYQ-U / RXYQ-U

          VRV IV+ heat pump



          Daikin‘s optimum solution with top comfort

            › Covers all thermal needs of a building via a single point of contact:     › Outdoor unit display for quick on-site settings and easy
           accurate temperature control, ventilation, hot water, air handling   read out of errors together with the indication of service
           units and Biddle air curtains                           parameters for checking basic functions.
            › Wide range of indoor units: possibility to combine VRV with stylish     › Free combination of outdoor units to meet installation space
           indoor units (Daikin Emura, Nexura, ...)                or efficiency requirements
            › Incorporates VRV IV standards & technologies: Variable Refrigerant     › Available as heating only by irreversible field setting
           Temperature, continuous heating, VRV configurator, 7 segment     › Contains all standard VRV features
           display and full inverter compressors, 4-side heat exchanger,
           refrigerant cooled PCB, new DC fan motor

                                                                           Up to 30m indoor unit
                                                                           height difference       ErP 2021
                                                                                                    COMPLIANT

                                                                                                Already fully compliant
               Access all technical information on RYYQ-U                                         to LOT 21 - Tier 2
               at my.daikin.eu or click here
                                                                                              Published data with
                                                                                             real-life indoor units
               Access all technical information on RXYQ-U
               at my.daikin.eu or click here

          Outdoor unit                      RYYQ/RXYQ   8U      10U     12U      14U     16U      18U     20U
          Capacity range                          HP    8       10       12      14       16      18       20
          Cooling capacity  Prated,c              kW   22.4     28.0    33.5     40.0    45.0     50.4    52.0
          Heating capacity  Prated,h              kW   13.7     16.0    18.4     20.6    23.2     27.9    31.0
                      Max.    6°CWB               kW   25.0     31.5    37.5     45.0    50.0     56.5    63.0
          Recommended combination                   4 x FXFQ50AVEB 4 x FXFQ63AVEB 6 x FXFQ50AVEB 1 x FXFQ50AVEB 4 x FXFQ63AVEB 3 x FXFQ50AVEB 2 x FXFQ50AVEB
                                                                              + 5 x FXFQ63AVEB  + 2 x FXFQ80AVEB + 5 x FXFQ63AVEB  + 6 x FXFQ63AVEB
          ηs,c                                     %   302.4    267.6   247.8   250.7    236.5   238.3    233.7
          ηs,h                                     %   167.9   168.2    161.4    155.4   157.8    163.1   156.6
          SEER                                          7.6     6.8          6.3              6.0          5.9
          SCOP                                              4.3          4.1         4.0          4.2      4.0
          Maximum number of connectable indoor units                             64  (1)
          Indoor index   Min.                          100.0    125.0   150.0    175.0   200.0   225.0    250.0
          connection  Nom.                                                        -
                      Max.                             260.0   325.0    390.0   455.0    520.0   585.0    650.0
          Dimensions  Unit    HeightxWidthxDepth  mm         1,685x930x765                1,685x1,240x765
          Weight      Unit                        kg      252 (RYYQ) / 198 (RXYQ)  319 (RYYQ) / 275 (RXYQ)  378 (RYYQ) / 308 (RXYQ)
          Sound power level Cooling  Nom.        dBA   78.0     79.1    83.4     80.9    85.6     83.8    87.9
          Sound pressure level  Cooling  Nom.    dBA        57.0        61.0     60.0    63.0     62.0    65.0
          Operation range  Cooling  Min.~Max.    °CDB                          -5.0~43.0
                      Heating  Min.~Max.        °CWB                           -20.0~15.5
          Refrigerant  Type/GWP                                               R-410A/2,087.5
                      Charge                    kg/TCO2Eq  5.9/12.3  6.0/12.5  6.3/13.2  10.3/21.5  10.4/21.7  11.7/24.4  11.8/24.6
          Piping connections Liquid  OD          mm         9.52                 12.7                 15.9
                      Gas     OD                 mm    19.1     22.2                     28.6
                      Total piping length  System  Actual  m                    1,000
          Power supply  Phase/Frequency/Voltage  Hz/V                        3N~/50/380-415
          Current - 50Hz  Maximum fuse amps (MFA)  A    20      25           32               40           50
          Outdoor unit System               RYYQ/RXYQ  22U   24U   26U    28U    30U   32U    34U   36U    38U
          System      Outdoor unit module 1            10     8            12                 16            8
                      Outdoor unit module 2            12    16     14     16    18     16    18     20     10
                      Outdoor unit module 3                                   -                             20
          Capacity range                          HP   22    24     26     28    30     32    34     36     38
          Cooling capacity  Prated,c              kW  61.5   67.4  73.5   78.5   83.9  90.0   95.4   97.0  102.4
          Heating capacity  Prated,h              kW  34.4   36.9  39.0   41.6   46.3  46.4   51.1  54.2   60.7
                      Max.       6°CWB            kW  69.0   75.0  82.5   87.5   94.0  100.0  106.5  113.0  119.5
          Recommended combination                    6 x FXFQ50AVEB  4 x FXFQ50AVEB 7 x FXFQ50AVEB 6 x FXFQ50AVEB 9 x FXFQ50AVEB 8 x FXFQ63AVEB  3 x FXFQ50AVEB  2 x FXFQ50AVEB  6 x FXFQ50AVEB
                                                    + 4 x FXFQ63AVEB + 4 x FXFQ63AVEB + 5 x FXFQ63AVEB + 4 x FXFQ63AVEB + 5 x FXFQ63AVEB + 4 x FXFQ80AVEB + 9 x FXFQ63AVEB + 10 x FXFQ63AVEB + 10 x FXFQ63AVEB
                                                           + 2 x FXFQ80AVEB     + 2 x FXFQ80AVEB        + 2 x FXFQ80AVEB + 2 x FXFQ80AVEB
          ηs,c                                     %  274.5  269.9  264.2  257.8  256.8  251.7  253.3  250.8  272.4
          ηs,h                                     %  171.2  167.0  164.6  166.0  169.8  163.1  166.2  162.4  167.5
          SEER                                         6.9   6.8    6.7       6.5          6.4       6.3   6.9
          SCOP                                         4.4   4.3       4.2       4.3       4.2       4.1   4.3
          Maximum number of connectable indoor units                             64  (1)
          Indoor index   Min.                         275.0  300.0  325.0  350.0  375.0  400.0  425.0  450.0  475.0
          connection  Nom.                                                        -
                      Max.                            715.0  780.0  845.0  910.0  975.0  1,040.0  1,105.0  1,170.0  1,235.0
          Piping connections Liquid  OD          mm       15.9                         19.1
                      Gas        OD              mm   28.6                   34.9                       41.3
                      Total piping length  System  Actual  m                    1,000
          Power supply  Phase/Frequency/Voltage  Hz/V                        3N~/50/380-415
          Current - 50Hz  Maximum fuse amps (MFA)  A             63                        80              100
          422