Page 224 - Каталог
P. 224
ПОСМОТРЕТЬ ВСЕ ТЕХНИЧЕСКИЕ
ЧЕРТЕЖИ RXYSQ-T8Y НА MY.DAIKIN.EU
Подробные технические чертежи
RXYSQ-T8V / / RXYSQ4-6 T8Y
RXYSQ-TV1
RXYSQ4-6TY1
2 Series installation
Obstacle above, too 500 or less
1 Stand-alone installation The relations between H, A and L are
500 or less as follows. 1000 or more
The relations between H, A and L are 1000 or more
as follows.
Set the stand as:
Close the bottom of the installation frame
Set the stand as: to prevent the discharged air from being
Close the bottom of the installation bypassed. 1500 or
frame to prevent the discharged air 250 or more Only two units can be installed for more
from being bypassed. this series.
2 Series installation (2 or more) (D) Double-decker installation
The relations between H, A and L are 500 or less 1 Obstacle on the discharge side Drain piping construction dimension
Close the gap A (the gap between the upper an lower
as follows. outdoor units) to prevent the discharged air from being
1000 or more Don not stack more than two units.
bypassed.
Set the stand as:
Close the bottom of the installation
frame to prevent the discharged air
from being bypassed. 1000 or
Only two units can be installed for 2 Obstacle on the suction side more
this series. 300 or more Close the gap A (the gap between the upper an lower
outdoor units) to prevent the discharged air from being
bypassed.
Pattern 2 Don not stack more than two units.
When the obstacle on the discharge side is lower Drain piping construction dimension
than the unit:
(There is no height limit for obstructions on the
intake side.)
No obstacle above
(E) Multiple rows of series installation 300 or
1 Stand-alone installation 100 or more (on the rooftop, etc.) more
500 or more 1 One row of Stand-alone installation
2 Series installation (2 or more)
The relations between H, A 100 or
more
and L are as follows.
2000 or more
200 or more
2 Rows of series installation (2 or more) 1000 or more
The relations between H, A and L are as follows.
Obstacle above, too
1 Stand-alone installation 1500 or more
Can not be installed
The relations between H, A and L are
as follows.
500 or less
Set the stand as: 1000 or more
Close the bottom of the installation
frame to prevent the discharged air
from being bypassed.
3000 or more
600 or more
1000 or more 1500 or more
3D045696D
222