Page 222 - Каталог
P. 222
ПОСМОТРЕТЬ ВСЕ ТЕХНИЧЕСКИЕ
ЧЕРТЕЖИ RXYSCQ-TV1 НА MY.DAIKIN.EU
Подробные технические чертежи
RXYSCQ-TV1
RXYSCQ-TV1
2 Series installation
Obstacle above, too 500 or less
1 Stand-alone installation The relations between H, A and L are
500 or less as follows. 1000 or more
The relations between H, A and L are 1000 or more
as follows.
Set the stand as:
Close the bottom of the installation frame
Set the stand as: to prevent the discharged air from being 250 or more
Close the bottom of the installation bypassed. 1000 or more
frame to prevent the discharged air 250 or more Only two units can be installed for
from being bypassed. this series.
2 Series installation (2 or more) (D) Double-decker installation
The relations between H, A and L are 500 or less 1 Obstacle on the discharge side 250 or
as follows. Close the gap Z (the gap between the upper an lower more Drain piping construction dimension
outdoor units) to prevent the discharged air from being
1000 or more bypassed.
Don not stack more than two units.
250 or
Set the stand as: more
Close the bottom of the installation
frame to prevent the discharged air
from being bypassed. 1000 or more
Only two units can be installed for 2 Obstacle on the suction side
this series. 300 or more Close the gap Z (the gap between the upper an lower
outdoor units) to prevent the discharged air from being
bypassed.
Pattern 2 Don not stack more than two units.
When the obstacle on the discharge side is lower 250 or Drain piping construction dimension
than the unit: more
(There is no height limit for obstructions on the
intake side.)
No obstacle above
(E) Multiple rows of series installation 300 or
more
1 Stand-alone installation (on the rooftop, etc.)
100 or more
1 One row of Stand-alone installation
500 or more
2 Series installation (2 or more)
The relations between H, A 100 or more
and L are as follows. 250 or more 2000 or more
250 or more
200 or more
1000 or more
2 Rows of series installation (2 or more)
The relations between H, A and L are as follows.
Obstacle above, too
1 Stand-alone installation 1500 or more
Can not be installed
The relations between H, A and L are
as follows.
500 or less 250 or more
Set the stand as: 1000 or more 250 or more
Close the bottom of the installation
frame to prevent the discharged air
from being bypassed.
3000 or more
1000 or more 600 or more
1500 or more
3D089310A